| Nominal size: | 63mm |
| Scale range: | -0.1 to 0.1 MPa (customized range as per request) |
| Accuracy: |
20℃: Class 1.0 or 1.6 -20℃ to +60℃: Class 2.5 -30℃ to -20℃: Class 3.0 |
| Degree of protection: | IP65 |
| Ambient conditions: | -30℃ to +60℃ |
| Leakage rate: | < 1*10-9 Pa.m³/s (Helium mass spectrometer) |
| Pressure connector: | G1/4'', NPT 1/4'', M20*1.5 (customized) |
| Location: | Center back |
| Electrical connection: | Compact plug cable box with M20*1.5 cable gland |
| Cable size: | 1.5mm; 2 recommended; 2.5mm maximum |
| Insulation properties: |
Insulation resistance >100 MΩ (500V DC) Withstand voltage 2kV, 50/60 Hz 1 min (to case) |
| Contact type: |
Pointer driven magnetic snap action signal contacts 80%Ag, 20%Ni, 10μm Au plated |
| Contact ratings: | 30W/50VA, 1A max; 220VDC/380V 50/60Hz max |
| Window: | Safety glass or instrumental glass |
| Weight: | 0.5 KG |
Automatically adjusts for thermal effects using bi-metal strips or digital sensors, providing stable readings at varying temperatures.
Configurable alarm and lockout contacts trigger signals when gas density drops below preset thresholds, enabling timely maintenance or system shutdown.
Available in all-stainless steel construction with optional oil filling for enhanced shock and vibration resistance.
By detecting whether SF6 gas is leaking. When a gas chamber leaks, the density indicated by the gas density meter decreases, triggering an alarm signal, alerting the operators to take timely measures to ensure operational safety.