| Nominal Size | 63mm |
| Scale Range | -1 to 1 bar (Customizable) |
| Accuracy | 20℃: Class 1.0 or 1.6; -20℃ to +60℃: Class 2.5; -30℃ to -20℃: Class 3.0 |
| Degree of Protection | IP65 |
| Ambient Conditions | -30℃ to +60℃ |
| Leakage Rate | < 1*10⁻⁹ Pa.m³/s (Helium mass spectrometer verified) |
| Pressure Connector | G1/4", NPT 1/4", M20*1.5 (Customizable) |
| Connector Location | Center back |
| Electrical Connection | Compact pluggable box with M20*1.5 cable gland |
| Cable Size | 1.5mm² (Recommended); 2.5mm² (Maximum) |
| Insulation Properties | Insulation resistance >100 MΩ (500V DC); Withstand voltage 2kV, 50/60 Hz 1 min (to case) |
| Contact Type | Pointer driven magnetic snap action signal contacts; 80%Ag, 20%Ni, 10μm Au plated |
| Contact Ratings | 30W/50VA, 1A max; 220VDC/380V 50/60Hz max |
| Window Material | Safety glass |
| Weight | 0.5 KG |
Automatically adjusts for thermal expansion effects using bimetal strips or digital sensors, providing highly accurate and stable readings across varying operating temperatures.
Configurable alarm and lockout contacts trigger emergency signals when gas density drops below preset thresholds, enabling timely preventative maintenance or automated system shutdown.
Constructed with high-grade stainless steel featuring optional silicone oil filling for significantly enhanced shock and vibration resistance in extreme environments.
Optional integration with RS485 digital output or wireless transmission protocols (e.g., LoRa) to seamlessly connect with smart grid management systems for real-time monitoring.
Continuous monitoring of SF6 gas levels during high-voltage operations to trigger automatic lockouts if gas density drops below safety limits.
Ensures long-term hermetic sealing and operational safety of critical GIS compartments exposed to harsh ambient conditions.
Provides crucial protection against severe internal electrical faults caused by gradual gas loss or pressure drops over time.